Groundbed
A groundbed is an array of electrodes, installed in the ground to provide a low resistance electrical path to ground or earth. A groundbed is a component in an earthing system.
Each electrode is called a ground rod or an earth electrode.
Grounding systems
For building electrical grounding systems or earthing systems, there is a low resistance conductor bonding the metalwork and this is connected to a groundbed. The electrodes for electrical grounding are often called ground rods and are often made from steel with a copper clad surface – typically 1 to 2 m long and 20 mm in diameter. These are driven vertically into the ground and bonded together with bare copper wire. Other grounding electrodes may include buried solid plates, or a grid of buried wires, where soil conditions do not favor driven ground rods. Buried metallic piping systems, well casings or the reinforcing bars of concrete slabs in contact with the earth have all been used as grounding electrodes.
Soil conditioning
Various materials may be placed around the ground rod to improve conductivity. These include:
- Ufer ground
- Bentonite clay
- Marconite
Cathodic protection
In cathodic protection, the anode groundbed is the arrangement of anodes in the ground or water and it provides the path for protective current to leave the anodes and enter to electrolyte.
High voltage direct current systems
In a high voltage direct current transmission system, each converter station may be equipped with a substantial ground bed to facilitate earth return operation of the system. In normal operation of a bipolar HVDC system, current is carried on the two wires of the transmission line, but if a line fails or one converter fails, the earth return can be used to maintain partial operation. Ground beds must be designed to accept considerable current ( on the order of 1000 amperes) for extending times, without drying out. Ground return operation may cause objectionable earth currents that cause corrosion of other buried services such as pipelines. A short overhead power line may be run from the converter station to obtain the best location for a ground bed.
References
References
- Electrical Engineer's Reference Book, Sixteenth edition by M. A. Laughton CEng., FIEE and D. J. Warne CEng., FIEE, Newnes, 2003, {{ISBN. 0 7506 46373
- "Soil conditioning agents".
- (October 1998). "Achieving an Acceptable Ground in Poor Soil".
- "Marconite".
- W.R. Jones, ''Bentonite Rods Assure Ground Rod Installation In Problem Soils'', 1980, DOI: 10.1109/TPAS.1980.319556
- NACE/ASTM G193 – 10a Standard Terminology and Acronyms Relating to Corrosion 2010
This article was imported from Wikipedia and is available under the Creative Commons Attribution-ShareAlike 4.0 License. Content has been adapted to SurfDoc format. Original contributors can be found on the article history page.
Ask Mako anything about Groundbed — get instant answers, deeper analysis, and related topics.
Research with MakoFree with your Surf account
Create a free account to save articles, ask Mako questions, and organize your research.
Sign up freeThis content may have been generated or modified by AI. CloudSurf Software LLC is not responsible for the accuracy, completeness, or reliability of AI-generated content. Always verify important information from primary sources.
Report